CEL-C - CHICAGO APPROVED EDGE-LIT
The Exit Store’s Recessed Chicago Approved Edge Lite Series Exit combines elegance with maximum Illumination to produce a contemporary styled exit sign that will enhance any decor.
POWER CONSUMPTION
- 120 OR 277 VAC Input
- AC Models 120 VAC : 9.6W
- AC Models 277 VAC : 9.2W
- Emergency Models 120 VAC : 10.6W
- Emergency Models 277 VAC : 10.2W
- Power Factor: (All Models) 0.85 Lagging
FEATURES
- Wall Recessed or Ceiling Recessed Models
- All metal construction
- Full stroke directional indicators
- 25 year Life WHITE LED light source
- 1 1/2 Hour Emergency Battery Backup
- City of Chicago Approved
- UL Listed to CCEA requirements
- Plenum Approved
FACTORY INSTALLED OPTIONS
ADDER DESCRIPTION
- -BK Matte Black Trim Plate
- -DB Dark Bronze Trim Plate
- -BA Brushed Aluminum m Trim Plate
- -SP Special Paint
- -SX Self Diagnostics (Battery Backup only)
STYLE
SINGLE FACE SIGNS
STYLE DESCRIPTION
- SE3 EXIT (Plain-No Arrow)
- SE6 EXIT (Right Arrow)
- SE9 EXIT (Left Arrow)
- SE12 EXIT (Double Arrow)
- SS2 STAIRS (No Arrow)
- SS5 STAIRS (Right Arrow)
- SS8 STAIRS (Left Arrow)
- SS11 STAIRS (Double Arrow)
DOUBLE FACE SIGNS
STYLE DESCRIPTION
- DE18 EXIT (Plain-No Arrow)
- DE21 EXIT (Left or Right Arrow)
- DE24 EXIT (Double Arrow)
- DS17 STAIRS (No Arrow)
- DS20 STAIRS (Left or Right Arrow)
- DS23 STAIRS (Double Arrow)
Construction
Housing and Cover/Trim: LED-XFO-C Series surface
mount housings and covers are constructed of heavy
gauge steel finished in white baked-on powder paint
providing scratch and corrosion resistance. Optional
black (-BK) and dark bronze (-DB) finishes are available,
see Options on front for ordering details.
LED-RXFO-C Series recess mount model housings are
constructed of heavy gauge steel with a steel ceiling trim
plate finished in white baked-on powder paint providing
scratch and corrosion resistance. Optional trim plate
finishes include black (-BK), dark bronze (-DB), polished
brass (-PB) and brushed aluminum (-BA), see Options on
front for ordering details.
Exit Panels:All models utilize acrylic exit panels with
screened on letters. Panels may be supplied with red or
green letters and a choice of white or mirrored mylar backgrounds.
Panels may also be specified with white letters
and a choice of red or green backgrounds.
Exit Face
Letter Size: 6†letters with 3/4†stroke
Directional Indicators: Screened on chevron arrows sized
to meet UL visibility requirements.
Illumination
Light Source:Exit face illumination is provided by a special
high intensity indirect white LED lighting strips. Letter
brightness and illumination uniformity exceed UL requirements.
LED Lamp Life: 25 years (estimated average)
Installation
Surface Mounting:Universal housing knockouts are
provided for direct attachment to standard 3 1/2†and 4â€
electrical boxes in wall, ceiling or end mount applications.
Recess Mounting: Recess models allow unit installation in
both suspended T-grid and wood framed ceiling applications.
Power Consumption
- AC Models 120V=9.6W277V=9.2W
- Emergency Models 120V=10.6W 277V=10.2W
- Power Factor (all models): 0.85 lagging
Code Information
All models are EnergyStar compliant, UL Listed and meet
NFPA 101 Life Safety Code, NEC, OSHA and City of
Chicago codes. Emergency models are UL924 Listed.
Charger and Electronics
Charger Type: Emergency models utilize a fully automatic,
temperature compensating, variable rate type charger
- Utility Input: 120/277VAC, 60 Hz.
- Temperature Range: 68ºF to 86ºF (20ºC to 30ºC)
- Recharge Duty Cycle: 24 hours
- Load Transfer: Solid state transfer circuit
- Controls:Test switch and LED AC-On indicator light
- Safety Circuitry: AC Lockout: Prevents battery discharge prior to initial
unit power-up saving installation time.
- Low Voltage Battery Disconnect: Protects the battery
from being severely damaged by deep discharge during
prolonged power failures.
Emergency Operation
Upon failure of the normal utility power, a solid-state transfer
switch automatically activates the emergency lamp. The
battery is protected from deep discharge through the use of a
low voltage disconnect circuit. Upon resumption of the normal
utility power the battery is disconnected from the load and
recharged through a solid-state charging circuit.
Optional Self-Diagnostic Circuit
The optional SX self-diagnostics circuit automatically performs a 15-minute
diagnostic/discharge test of the unit every 30 days. The SX circuit checks for
proper battery capacity and emergency lamp operation. Malfunction of the
battery or lamp(s) detected during diagnostic cycles will be indicated by the
units LED status indicator.
Battery
LED-XFO/RXFO-C Series exit signs are provided with a sealed maintenance free
lead calcium battery that will provide many years of dependable service.
Warranty Unit: (including LED lamps) 3-years full coverage against defects in materials
and workmanship from date of shipment.
- Battery: 3 years full warranty plus an additional 7 years of pro-rata coverage.
WARRANTY
The Exit Store guarantees each product to be free from defects to the original purchaser for a period of 3 years from the date of purchase.If any component is found to be defective, The Exit Store will repair or replace the defective component at their option.
Warranty does not cover damage caused by improper installation, misuse, abuse, improper environmental conditions, unauthorized modifications or shipping damage.Damage caused by explosions, water leaks, fire, war or acts of God are also not covered.