50-75 Watt 12 VDC EMERGENCY POWER FOR
SUPPORT OF OUTDOOR
EMERGENCY LUMINAIRES
PRODUCT OVERVIEW
The CPM Series emergency power module
is designed to support 12 VDC outdoor or indoor
emergency luminaires located within close proximity
of an emergency exit. The CPM power module can
be recessed into either a mechanical or sheetrock
ceiling and emergency power routed to building
mounted exterior emergency luminaires and/or
emergency
luminaires located inside the building. The
CPM Series emergency power module offers an
inconspicuous alternative to wall-mounted emergency
products used to support remote emergency luminaires.
ILLUMINATION
The CPM Series is a suggested emergency power
source for the PathMaster interior/exterior low
level
LED Luminaire, the CEF MR16 exterior wall/soffit
remote, and the CRE recessed MR16 exterior
remote. (See back page)
Any 12 VDC remote emergency luminaire can also be
powered by the CPM power module.
INSTALLATION
The CPM Series, when installed in a mechanical
ceiling system, utilizes a metal rough-in enclosure
that can be secured to the ceiling structure via an
optional bar hanger kit or via support cables
suspending
the unit from permanent building structures.
Sheetrock ceiling installations allow the rough-in
enclosure to attach to ceiling joists via screw hole
knockouts in the enclosure. The trim plate is secured
to the rough-in enclosure via four oval head screws.
A safety hook device is supplied to support the trim
plate during installation.
HOUSING
The CPM power module rough-in enclosure is fabricated
from 20 gauge die formed galvanized steel.
The trim plate is fabricated from 12-gauge steel and
is painted with a matte white powder coat finish.
The trim plate is also offered with an optional matte
black finish.
Knockouts for conduit as well as screw hole knockouts
for mounting to joist are conveniently located
on the back box.
ELECTRONICS
120/277 VAC, 60 Hz, Dual Input
The CPM Power module utilizes an automatic voltage
regulated charging system.
The 2-state charger eliminates the need for periodic
battery exercising.
It is recommended that a monthly load test of a
minimum
of (1) minute be performed and recorded to
satisfy NFPA 101 life safety requirements.
A momentary test switch and normal power indicator
lamp are located on the trim plate to assist testing
and visual inspection of the product.
A pre-wired plug in receptacle is provided within the
enclosure for routing 12 VDC emergency power to
remote emergency luminaires.
BATTERY
The CPM Power module is supplied with maintenance
free
sealed lead calcium battery with a designed 5-year
service
life. The CPM50 Power module uses (2) 100-1-136
batteries.
The CPM50 Power module will supply 50 watts at 12VDC
for
90 minutes. The CPM75 uses two 100-1-188 batteries
and
will supply 75 watts at 12 VDC for 90 minutes.
OPERATING TEMPERATURE RANGE
Standard Unit: 65°F (19°C) to 85°F (30°C)
Damp Location: 50°F (10°C) to 104°F (40°C)
CODE COMPLIANCE
UL 924 listed
NFPA 101
UL924 Damp location listed optional* (50° F to
104°F)
*50 watt models only
ELECTRICAL SPECIFICATIONS
CPM50
120 VAC .22 A
277 VAC .11 A
CPM75
120 VAC .21 A
277 VAC .11 A
CPM50DL
120 VAC .22 A
277 VAC .11 A
WARRANTY
Three year full electronics warranty
One year full plus four year prorated lead
calcium battery warranty
ALL SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE.
|