ECONOSINE (500-3000 VA)
FEATURES
Single Phase
500 - 3000 VA
HID, Incandescent, Fluorescent
U.L. 924, 924A Listed
Small Footprint, Lightweight
Sine Wave Output
Front access and Easy Installation
STANDARD FEATURES
Low Profile Compact Cabinet
Single Phase, Full Range Voltage Regulation
AC Power ON Indicator
Battery ON Indicator
Charger ON Indicator
DC Battery Switch
AC Line Switch
SPECIFICATIONS
Sizes:500, 1250, 1500, 2000, and 3000
Input Voltage:120 Volt Only +10% On-Line
zero Transfer time, 277 Volt Input with
external Isolation Transformer Only
Output Voltage:120 Volt Only, or 277
Volt with external Isolation Transformer Only
Output Frequency:60 Hz. +5%
Output Voltage Reg.:+4% for all loads and
for Battery Discharge mode
Output Wave Form:Sinewave during emergency
a 10% max. THD with linear load
Output Protection:Current limiting and
short circuit protection
Efficiency:70% minimum @ normal mode
Battery:Maintenance free sealed lead calcium
48 VDC for 500, 750, & 1000 VA
72 VDC for 1250, 1500, & 2000 VA
Recharge Time:Recharge Time per U.L. 924
Environmental:Humidity: 0 - 95% RH w/no condensation
Operating Temp.:
UPS: 0°C to +40°C. (-32°F to 102°F)
Battery: 20°C to +30°C. (68°F to 86°F)
EXTERNAL ISOLATION TRANSFORMER
Isolation Transformers must be used on all input or output voltages other than 120. By using the Isolation Transformer, you have the choice of 208 or 240 or 277 Volts on the input or output.
Note, these are all externally mounted.
|