ARCHITECTURAL RECESSED CEILING OR WALL
EMERGENCY LIGHTING, BATTERY INCLUDED
PRODUCT OVERVIEW
Fusion is a fully recessed, architectural emergency
lighting unit. Suitable for wall or ceiling
mounting, Fusion remains unobtrusive even when
illuminated. Fusion provides an alternative to
standard
wall mounted emergency lighting.
ILLUMINATION
Illumination is provided by two high performance
35 watt MR16 lamps combined with a patented
reflector system. Optical assemblies can be rotated
from 0°to 90° for corner installations. Wall mounted
versions can generate an average of 1 footcandle
of emergency illumination over a 3ft x 60ft egress
path, while ceiling mounted versions can broadcast
an average of 1 footcandle over a 3ft x 90ft egress
path. The lamps remain hidden during emergency
illumination. IES photometric data files are
available upon request.
INSTALLATION
The Fusion series is supplied with ceiling mount
optics. Wall mount units require the wall mount
lens kit accessory (WMLK). Mechanical or
sheetrock ceiling installation is enabled using
optional bar hangers or structural support wire
(supplied by others).
HOUSING
Backbox constructed of 20 gauge galvanized steel.
Flush cover and diffusers constructed of impact
resistant
polycarbonate.
White faceplate is standard, with optional black
housing
available.
Faceplate may be painted or wallpapered to match
wall or ceiling decor.
Suitable for wall or ceiling mounting.
Wall mounted units can be fastened to wood or metal
studs from either the left or right side.
Mechanical ceiling mounting is accomplished with
grid ceiling bar hangers.
ELECTRONICS
120/277 VAC dual voltage input with surge-protected,
solid-state charging circuitry provides for a
reliable
charging system.
Fully automatic, voltage regulated charging system
will maintain battery at full capacity without the
need
for periodic equalization charge.
Charging system is complete with low voltage
disconnect,
AC lockout, brownout protection, AC indicator
lamp and test switch.
Optional ACCU-TEST self-diagnostics includes an
automatic 3 minute discharge test every 30 days. A
manual discharge test from 1 to 90 minutes is
available.
Real-time system checks occur automatically
every minute. Individual LED indicators illuminate
red
if either a battery, charger or lamp failure occurs.
CODE COMPLIANCE
UL 924 listed for insulated ceiling systems (IC
rated)
NFPA 101
NEC, BOCA and OSHA illumination standard
Meets ADA specifications for wall mounted
lighting fixtures
ELECTRICAL SPECIFICATIONS
.32 amps (120 VAC)
.14 amps (277 VAC)
BATTERY
The battery shall be maintenance free, sealed lead
calcium. The sealed lead calcium battery shall
provide trouble-free operation in temperatures up to
85°F
(30°C) and is supplied with a one year full
warranty.)
CHARGING CIRCUITRY
Unit shall utilize a fully automatic, voltage regulated charging system. The charging system shall maintain the battery at full capacity without
the need for periodic exercising or equalization. The following features shall be standard: Low voltage disconnect (LVD), brownout protection and AC lockout. Optional
self-diagnostics shall monitor and indicate a fault occurring in either the charger, battery, lamp circuit, or input supply.
WARRANTY
Three-year full electronics warranty.
One year full plus four year prorated lead
calcium battery warrenty