WAVE RIDER I (3-20 KVA)
FEATURES
CSA Listed to UL 924, UL1778
3, 5, & 7.5 kVA in one cabinet
10, 12.5, 15, & 20 kVA one inverter and only one battery cabinet
Battery management system
Battery exerciser
True no break power to the load
LCD panel for monitoring of continuous self diagnostic
Seismic rated with bracket kit.
RS 232 & RS 485
90% Efficiency
Pulse width modulated (PWM) generator compatible
Sinusoidal wave
Incandescent, Fluorescent, HID, HPS
Power factor & energy efficient ballast.
Global Monitoring System Option
Battery Management System
SPECIFICATIONS
Power Rating:3, 5, 7.5, 10, 12.5, 15, and 20 KVA
Input Voltage:3 & 5KVA ....120, 208, 240, or 277 VAC
(-20% to +15%)
7.5, 10, 12.5, 15, & 20kVA ...... 208,
240 or 277VAC (-15% to +15%)
Output Voltage:3, 5, 7.5, 10, 12.5, 15, & 20 .... 208,
240 or 277VAC
Output Frequency:(Inverter Operation): 60Hz +0.5Hz.
Output Voltage Reg.:+3% Regulated within CBEMA curve
Output Wave Form:Sine-wave
Input Protection:Input circuit breaker provided
protection to the unit, load and personnel. Input
Circuit Breaker will be higher interruption
rated 42 (KAIC) breaker as standard.
Output Protection:Internal Electronic
overload protection. Circuit breaker provides
inherent over-load protection. Factory selectable
voltage 120, 208, 240, or 277 for input or output
voltages. If input is different from output or
output different from input, an internally mounted
transformer is required.
Serge Protection:The inverter will protect itself and the load against
surge as defined in ANSI/IEEE C62.45 category A and B.
Power Factor:0.7
Isolation:Output is completely isolated from input,
and with multi voltages, when input & output is different.
Noise Isolation:-120 dB. Common-Mode.
60 dB. Transverse-Mode
Efficiency:90% minimum
Crest Factor:3.1 Typical (may vary by model)
Battery:Sealed maintenance free
Battery Mngmnt System:Utilizes a microprocessor technology to monitor the batteries critical levels and apply charging cycles
in a method to substantially increase battery life.
Housing:Free standing NEMA 1 Enclosure Power coated
paint Front access only Multiple conduit entries
Refer to chart for dimensions
Recharge Time:Approx. 16 times discharge rate
Environmental:Humidity: 0-95% RH w/no condensation Operating temperature:
UPS: 0°C to +40°C. (-32°F to 102°F)
Battery: 20°C to +30°C. (68°F to 86°F)
Storage temperature: -20 to 60C.
Safety Agencies:CSA Listed to UL924, UL924A, & UL1778
|