ON-LINE INVERTER (UNINTERRUPTIBLE) (5-20 KVA)
FEATURES
3 to 20 kVA - Single Phase UL924 Listed Manufactured for Hostile Environments Outdoor Applications Remote Locations Incandescent, Fluorescent, or HID INPUT SPECIFICATION
Nominal Input Voltage: 120, or 208, or 240, or 277 VAC single phase Input Voltage Range: +20% to -35% Input Frequency: 60 Hz +5% Power Factor: 0.7 Overcurrent Protection: Circuit breaker Power Connection: Hard wired (terminal block) Input Configuration: 2 wire (hot, neutral) plus ground OUTPUT SPECIFICATION
Output Rating: 3, 4.4, 5.4 , 8, 10, 15, and 20 kVA (Normal Mode/Emergency Mode) Voltage: 120/240, 277 VAC, Single Phase Voltage Regulation: +3% No Load to Full Load; +3% High Line to Low Line Frequency: 60 Hz +0.25 Hz (When on Inverter) Waveshape: Sine Wave Harmonic Distortion: <7% THD; <5% Single Harmonic Crest Factor: Up to 3 to 1 Power Factor 0.7 Overload: 125% for Ten (10) Minutes; 150% Surge Protection: Fault Current Limited by Ferroresonant Design Noise Rejection: -120 dB Common Mode; -60 dB Normal Mode Operating Temp: Tested for -29F(-34C) to 136F(58C) PHYSICAL SPECIFICATION
Accessibility: All Servicing is through the Front. Cable Entry: Bottom Mounting: Four (4) Mounting Holes Provided to Anchor Enclosure to Pedestal BATTERY SPECIFICATION
Battery Run Time: 90 min Battery Type: Sealed, Maintenance-Free, Lead calcium Nominal DC Link: 48 or 120 VDC link Overcurrent Protection: Circuit Breaker