TWO THREE-WATT DIMMABLE LED LAMP -- TWO-CIRCUIT OPTION FOR EMERGENCY LIGHTING

PRODUCT OVERVIEW

Splendore is a state of the art architectural emergency lighting product based on high-output white LEDs. The normally on mode may be locally switched or dimmed and an optional two-circuit input is available for emergency illumination powered by a generator or inverter system. It is available in a wide range of decorative finishes to blend with any setting. Die cast exits with complementary finishes are also available.

ILLUMINATION

Illumination is provided by two 3 watt, white LEDs and a specular Miro 4 (Alanodâ„¢) aluminum reflector. The lamp head assembly may be rotated in five-degree increments over a range of 60 degrees for ideal distribution along the egress path. Splendore will provide one foot-candle average illumination over a 12ft long path of egress for a single fixture and 26ft centers for multiple fixtures. IES photometric data files are available, on our website.

INSTALLATION

Splendore is designed to be wall mounted to a 3-1/2in octagonal junction box. Installation is quick and easy using simple two-piece snap together construction. The backplate is provided with convenient keyhole slots for mounting and a tamperproofing option is available.

HOUSING

Housing construction shall be of cast and extruded aluminum. The unit shall be available in multiple colors and finishes. The unit shall be wall mounted to a standard 3-1/2in octagonal junction box.

ELECTRONICS

120/277 VAC dual voltage input.

ELECTRICAL SPECIFICATIONS

Input Power Requirements at 120 VAC
120 VAC - 0.10 Amps - 11.73 Watts

Input Power Requirements at 277 VAC
277 VAC - 0.04 Amps - 11.61 Watts

MODES OF OPERATION

AC Only-Accommodates 120/277 VAC dual input. This model may be controlled by a wall switch or dimming circuit.

2CKT1-Offers the AC-only input but includes a 120/120 utility and emergency feed from a generator or AC inverter system for egress lighting.

2CKT2-Offers the AC-only feature but includes a 277/277 utility and emergency feed from a generator or AC inverter system for egress lighting.

CODE COMPLIANCE

  • UL 924 and 1598 Listed
  • UL damp location listing standard
  • NEC, BOCA and OSHA illumination standard.

  • WARRANTY

  • Three year full electronics warranty.
  • OPERATING TEMPERATURE RANGE

  • -22°F (-30°C) to 104°F (40°C)


  • ALL SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE.
    Options Info
    Color
    • White *Standard
    • Black
    • Aluminum (+$10)
    • Gunmetal (+$10)
    • Ornamental Bronze (Texture) (+$10)
    • Aged-Copper (+$10)
    • Velvet Green (+$10)
    • Nickel (+$10)
    Options
    • 120/120 2 Circuit Input for Emergency feed from generator (+$25)
    • 277/277 2 Circuit Input for Emergency feed from generator (+$25)
    • Tamperproof Hardware (Torx bit included) (+$12)
    Accessories
    • Tamperproof Screwdriver (T10 bit and driver included) (+$19)
    Related Products
    Exit Sign, Exit Light - The Exit Store

    My Cart Cart | My Account | Check Out | Site Map
    Customer Service | 1.866.471.2849 | New Account | Sign In