skip to navigation

THE EXIT STORE Exit and Emergency Specialists

Sirocco NEMA 4X Wet Location LED Exit Sign

Sirocco NEMA 4X Wet Location LED Exit Sign

Purchasing Info

Base Price:
$239.00
Shipping Weight:
8.00 .lbs

NEED HELP?

866.471.2849

7am-7pm PST

Select Configuration

Operation
Legend
Faces
Face Color
Housing Color
Options

Reset Configuration*

*As you select options, the configuration tool is equipped with active filtering to ensure valid combinations.

OVERVIEW

  • Download SRWE Spec Sheet

  • Download SRWE Installation Instructions

    Sirocco NEMA 4X Wet Location LED Exit Sign

    PRODUCT OVERVIEW

    NEMA-4X and NSF certified, the Sirocco SRWE Series LED Exit Sign delivers impressive, state-of-the-art illumination in a visually appealing package.
    The Sirocco SRWE Exit Series is designed for use in a wide range of commercial and industrial environments where resistance to humidity, dust, water infiltration and vandalism are specification criteria.

    The Sirocco SRWE Exit Unit is designed and engineered with style in mind and sets new standards for emergency lighting in today's toughest environments. Whether it is a large warehouse, heavy-duty plant or food processing installation, the Sirocco series, is the solution for all your industrial emergency lighting. Its tamper-proof revolutionary compact design (Patent pending) makes it also suitable for commercial applications as well as for schools or public facilities. The sign is available in single or double-face configurations. High-efficiency LED's evenly illuminates the exit signage. The unit has great versatility allowing for end, ceiling or wallmount, single face or double face installation.

    Quick Glance

    Voltage Housing Colors Listing Dimensions
    120v-277v White, Black, Gray(Aluminum) UL 924 Listed 13 1/4" x 3 7/16" X 9 3/16"
    Hertz Letter Colors Exit Illumination Body Material
    50Hz/60Hz Red, Green LED PVC
    Face Count Chevrons DC power Mounting
    Single/Double Knock Out 6 to 48vdc Top, Back, End
    ADA Options Testing Method Consumption NEMA Rating
    Flasher, Buzzer Automatic Less than 3.7w 4x, NSF

    FEATURES

    High Performance Circuitry
    • Self powered units have batteries and circuitry located inside the durable exit housing.
    • Continuous self-diagnostic monitoring. (Self Powered Version)
    • Self Powered units have fully automatic solid state charger.
    • AC, AC/DC and Self-Powered Models have universal, 2-wire input 120V to 277VAC 50/60 Hz.
    • Batteries are sealed, maintenance-free Nickel-Cadmium for superior performance and long life.
    • Provides 90 minutes of emergency operation.
    • Batteries recharge per UL924 requirements.
    • Self-testing in accordance with NFPA101
    • Each unit comes standard with one tamper-proof driver bit.

    SPECIFICATIONS

    Overview

    The Sirocco Series Exit is offered in AC-Only, AC/DC or Self-Powered configurations. The industrial grade polyvinyl chloride enclosure is designed specifically for hostile environment applications. The Sirocco Series is fully gasketed around lens and canopy. The sealed faceplate is constructed of heavy duty, vandal resistant polycarbonate and features an evenly illuminated legend. The stencil-face has knock-out directional chevron arrows. A magnetic test switch adds to the ruggedness of the Sirocco Series design by reducing the chance of tampering and damage.

    The Sirocco Exit Series is designed specifically for high abuse areas, wet locations, and cold weather applications. It is ideally suited for schools, parking garages, public areas, transit platforms, and security areas/prisons.

    Advanced Circuitry

    Self-Diagnostic circuitry is standard on all self-powered models. This circuitry is programmed to ensure the exits readiness and reliability by continuously monitoring every critical function of the unit. If a problem occurs, a single service required indicator illuminates immediately. A detailed diagnostic display is located on the inside of the exit sign, out of sight from the general public that will further indicate the nature of the fault. The self testing software will test the unit for 30 seconds every 30 days, 30 minutes every 60 days and 90 minutes annually.

    Housing

    The signs are listed to UL924. The exit housing is molded polyvinyl chloride available in either white or black. A universal mounting pattern is available on single face signs for back mounting to a wall or surface. All models come equipped with a canopy for ceiling or end mount applications. The faceplate and canopy have gasketing available for a secure, water-tight seal. Vandal proof screws are provided for securing the faceplate(s).

    Illumination

    Long-life light emitting diodes (LED’s) provide even illumination, at the same intensity during AC operation and in the the emergency mode. LED’s are mounted within the exit housing but not along the face or wording. An LED sensitive ink diffuser mounted on the face to provides full 3/4” letter stroke with even illumination. LED technology is ALINGAP.

    Self Powered Models have a Nickel-Cadmium battery for long, maintenance-free life. In the emergency mode the battery provides a minimum of 90 minutes run time. Self Testing/Self diagnostics are standard on all self powered signs. The circuit has a single “service required” LED visible to the user. A detailed diagnostic display is located internally to the unit and isolates the fault to the battery charger board or LED lamps. The self testing software will simulate a power failure and transfer the light source to the battery for 30 seconds every 30 days, 30 minutes every 60 days and 90 minutes annually in accordance with NFPA 101. The unit is supplied with an AC pilot light and a magnetic proximity test switch for manual testing. The charger is fully automatic, solid state, temperature compensated and short circuit protected.

    Durability and Vandalism

    Rugged poly vinyl chloride body, will not dent, peel, rust or corrode. The sealed faceplate is constructed of heavy duty, vandal resistant polycarbonate and features an evenly illuminated legend. The fully gasketed faceplate is fastened with stainless steel tamper-resistant screws. Models can be wall, end or ceiling mounting. Legend and chevron complies with UL and CSA requirements.

    Environmental Suitability

    *AC only and AC/DC units are listed for use at -40°C to + 40°C Sirocco series exits signs are unaffected by the vibrations, ambient temperature swings and typical power surges detrimental to standard exit light sources.

    EMERGENCY OPERATION

    When in emergency mode the exit remains illuminated. The unit is capable of operating in the event of a power loss using self-contained battery for a minimum of 90 minutes per UL924. When AC power returns to the unit, the emergency power will turn off and the unit commences recharging.

    EXTERNAL SPECIFICATIONS

    Housing

    The Sirocco SRWE Exit's NEMA-4X rated housing can withstand moisture, dust and corrosion. The faceplates are molded of heavy-duty vandal-resistant polycarbonate and the rugged UV-stabilized thermoplastic body will not dent, peel or corrode. The unit is equipped with stainless steel tamper-proof screws. A special bit is provided with every unit and additional bits can be ordered separately (see accessories). The unit comes in a choice of three housing colors: white, black or gray. The unit is NSF Certified for use in food processing plants.

    Face Colors

    White, Black, Aluminum

    Housing Colors

    White, Black, Gray

    Mounting Ability

    The unit comes standard with a universal mount canopy kit allowing end, ceiling or wall-mount installation. A universal knockout pattern allows direct mounting on junction box. Knockouts are also available for conduit entry and are located on the top and both sides of the unit. An optional pendent top adapter can be added to extend the fixture down from the ceiling where high ceilings exist.

    Housing Material

    The housing is heavy-duty vandal-resistant polycarbonate and the rugged UV-stabilized thermoplastic body will not dent, peel or corrode. The unit is equipped with stainless steel tamper-proof screws. A special bit is provided with every unit and additional bits can be ordered separately

    Environmental Rating

    NEMA 4X, Vandal, High Abuse, Damp, Cold, Wet, Indoors or Outdoors locations within the temperature range: -40°C to + 40°C for AC and AC/DC units. Self Powered units are standard rated for (10C to 40C) (50F to 104F) but with Cold Weather Option are cold rated for (-20C°) (-4°F).

    DIMENSIONS

    Single Face

    Depth:3 7/16" Width:13 1/4" Height:9 3/16"

    Double Face

    Depth:3 7/8" Width:13 1/4" Height:9 3/16"

    SRWE Wet Location Exit Sign Dimension

    MECHANICAL SPECIFICATIONS

    The Sirocco Series Wet Location Exit unit is equipped with the fully automatic Advanced Diagnostic micro-controller board. The micro-controller tests, detects and indicates battery, charger circuitry, lamps or LED strip failures. An external LED signals a general service alarm while an internal diagnostic LED display indicates the nature of failure. The board is factory preset to non-audible diagnostic and a 15 minutes time delay. These functions can be enabled or disabled during installation. The equipment comes standard with a dual voltage input of 120/277 Vac and 60Hz. 120vac or 277vac dual circuit configuration is also possible. 6vdc-48vdc input is an option.

    Illumination Source

    High-efficiency ALINGAP LED's, evenly illuminate the legend of the Exit sign.

    Power Consumption

    1.2 W for AC and AD/DC versions and 3.7 watts for Self Powered Version.

    Remote Capacity

    This unit is capable of supporting a remote load capacity of 50 watts. Please see SRWC version .

    Charger

    Unit comes with a sealed, maintenance-free Nickel- Cadmium battery, and is suitable for wet and damp locations. Without the Cold Weather option the rating is: (10C to 40C) (50F to 104F)

    Self Powered Performance Testing

    This unit self-tests for 1 minute every 30 days, 30 minutes on the 6th month and 90 minutes every 12 months. The unit is capable of full recharge in compliance with UL specifications. The unit is supplied with a magnetic test switch. A "Service-Required" lamp is located near the test switch and flash when a fault is detected. A LED-based diagnostic display is located inside the equipment and identifies the source of failure (battery, charger, circuitry, or lamps). Optional Audible Diagnostics alert is available.
    You operate the magnetic "test switch" by holding the provided magnet near the AC pilot lamp, where indicated on the legend. This will initiate a one minute test. The DC lamps will illuminate for approximately one minute, then the unit will automatically return to stand by mode. Test can be cancelled by holding the magnet near the test switch again.

    There are five diagnostic indicators: one external and four internal. Unit must be opened to gain access to internal indicators. External: General alarm, "Service Required". The LED will turn-on if any alarm condition is detected. Internal: Battery Failure, Battery Disconnect, Charger Failure & Lamp Failure. Steady ON if alarm condition exists. Normal operation, No fault - "Service Required" is OFF. Faulty operation - "Service Required" is ON.

    This is a multi-function indicator related to battery condition.This indicator will be illuminated when a wrong battery (ex: 6V battery on a 12V system or vice versa) or a completely depleted battery (battery voltage less than 65% of nominal) is connected to the circuit - Allow 24 hours recharging if the battery voltage is between 25% and 65% of nominal - it will also be illuminated if the battery has failed a timed or forced test (reached LVD level before the end of the test). In the case of incorrect battery, the circuit will disable the charge current.

    Maintenance

    The charger first continuously recharges the battery then, when the battery is at full capacity, the charger periodically pulse charges the battery in stand-by mode. This pulse-type charger promotes long battery life and reduces the potential for grid corrosions. Its charge voltage is factory set to +/-1% tolerance and is temperature compensated. The charger incorporates Lockout and Brownout Circuits, and Low Voltage Disconnect. It protects the unit from over-current, short-circuit, and reverse polarity.

    INSTALLATION

    Mounting

    wall(back) or ceiling(top) single or double face. Optional Pendent Top Adapter for lowering the height of the unit when installed with high ceilings can be ordered.

    SRWE Wet Location Exit Sign Line Art
    Directional Indicators

    Knockouts allow you to select no arrows, left arrow, right arrow, or both arrows at installation time.

    Electrical Connections

    Using the sealed AC nipple/wire assembly (3 wires), connect one end to the transformer leads, inside the enclosure, and the other end, to AC line voltage inside the junction box. Connect the white lead to neutral and the green lead to ground. Connect the purple lead to AC line voltage and to appropriate transformer lead. Unused primary wire must be insulated to prevent shorting.

    • Standard Input: 120vac-277vac 50Hz/60Hz

    OPTIONAL FEATURES

    • Cold Weather Location - Extends the temperature rating of Self Powered Units (-4F to +104F)
      *Self Powered Only
    • Fire alarm activated flasher
    • Flasher/Buzzer - (AC power failure)
      **Cant be combined with Audible Diagnostics Option
    • Flasher - (AC power failure)
    • Canopy Pendant Mount
      Allows sign to extend down lower when top mounted on high ceilings
    • Advanced Diagnostics Audible
      Audible alerts when system detects irregularity.
    • Custom Faceplate *Consult Factory

    ACCESSORIES

    • Additional bit for tamper proof screws - one is provided with unit purchase by default

    APPLICATIONS

    • Hosedown areas/car washes
    • Transit platforms
    • Food processing/prep facilities
    • Sports arenas /swimming pools
    • Marine locations
    • Security areas / prisons
    • Chemical plants
    • Warehouse & cold storage facilities
    • Schools and other public facilities
    • Heavy industrial facilities

    COMPLIANCES

    UL924 Listed, NSF, NEMA 4X

    WARRANTY

    Unit Warranty

    5-year full warranty (excluding lamps and fuses).

    Battery Warranty

    Sealed Nickel-Cadmium Battery has a 10 year life expectancy and carries a 5-year Full Warranty, plus a 5-year pro rata warranty

    NEMA RATINGS

    NEMA 4X Certified for Wet and Damp Locations

  • back on top